**Topics that affect SIS:** | **Topics that affect SIS:** | ||
Line 30: | Line 30: | ||
- | There are many different types of expansion vessels. In smaller systems the membrane type with a fixed gas charge are the most commonly used.The advantage of an expansion vessel over an open header tank is that it is sealed from the atmosphere preventing oxygen entering the system. A rubber membrane separates the gas charge from the water side. The working principle of a fixed gas charge vessel can be seen in Tutorial 2 Fixed charge vessels are sometimes also referred to as variable pressure expansion vessels. | + | There are many different types of expansion vessels. In smaller systems the membrane type with a fixed gas charge are the most commonly used.The advantage of an expansion vessel over an open header tank is that it is sealed from the atmosphere preventing oxygen entering the system. A rubber membrane separates the gas charge from the water side. The working principle of a fixed gas charge vessel can be seen in this [[https://youtu.be/NO7r2aiNlRU|clip]]. Fixed charge vessels are sometimes also referred to as variable pressure expansion vessels. |
==== Membrane Expansion Vessel ==== | ==== Membrane Expansion Vessel ==== | ||
Line 248: | Line 248: | ||
<WRAP box 500px left> | <WRAP box 500px left> | ||
**<fs 80%> Vn = 100l \ \ \ \ \ Pf = 2.92 \ \ \ \ \ Ve = 22.2l </fs>** | **<fs 80%> Vn = 100l \ \ \ \ \ Pf = 2.92 \ \ \ \ \ Ve = 22.2l </fs>** | ||
- | * Vwr = 100l / 2.92 - 22,2l = 11.6l | + | * Vwr = 100l / 2.92 - 22,2l = 12l |
</WRAP> \\ | </WRAP> \\ | ||
++++ | ++++ | ||
- | ==== Cold Fill Pressure ==== | + | ==== Cold Fill Pressure (Pa) ==== |
Line 259: | Line 259: | ||
The cold fill pressure is at least: | The cold fill pressure is at least: | ||
- | **Pa=P0+0.3 barg** | + | <WRAP box 250px left> |
+ | **Pa = P0 + 0,3barg ** | ||
+ | * <fs 80%> Pa = Cold Fill Pressure </fs> \\ | ||
+ | * <fs 80%> P0 = Gass Fill Pressure </fs> \\ | ||
+ | </WRAP> | ||
- | In the example, a bigger vessel was chosen to accommodate an increased reserve of 11.6l | + | \\ |
- | To ensure that this reserve is pushed into the vessel the revised cold fill pressure needs to be calculated. | + | \\ |
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
- | **Pa=(Vn(P0+1)/(Vn-Vwr))-1** | + | In the above example, a bigger vessel was chosen to accommodate an increased reserve of 12l. |
+ | To ensure that this reserve is pushed into the vessel **the revised cold fill pressure** needs to be calculated. | ||
- | Pa=(100(1.3+1)/(100-11.6))-1 | + | <WRAP box 300px left> |
+ | **Pa = (Vn (P0+1) / (Vn-Vwr)) - 1 ** | ||
+ | * <fs 80%> Pa = Cold Fill Pressure </fs> \\ | ||
+ | * <fs 80%> Vn = Nominal size Expansion Vessel </fs> \\ | ||
+ | * <fs 80%> P0 = Gass Fill Pressure </fs> \\ | ||
+ | * <fs 80%> Vwr = Water Reserve </fs> \\ | ||
+ | </WRAP> | ||
+ | |||
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
+ | \\ | ||
+ | |||
+ | ++++Example| | ||
+ | <WRAP box 500px left> | ||
+ | **<fs 80%> Vn = 100l \ \ \ \ \ P0 = 1.3 \ \ \ \ \ Vwr = 12l </fs>** | ||
+ | * Pa = (100 (1.3+1) / (100-12l)) - 1 = 1.6 barg | ||
+ | </WRAP> \\ | ||
+ | ++++ | ||
- | Pa=1.6 barg | ||